STRATOS-Z
Design
Glandless circulating pump with screwed connection or flange connection, EC motor and automatic power adjustment.
Application
Secondary hot water circulation systems of all kinds, hot-water heating systems of all kinds, air-conditioning, closed cooling circuits, industrial circulation systems
|
Type key |
Example |
Wilo-Stratos-Z 40/1-8 |
Stratos |
High-efficiency pump (screw-end or flange-end pump), electronically controlled |
Z |
Single pump for secondary hot water circulation |
40/ |
Nominal connection diameter |
1-8 |
Nominal delivery head range [m] |
Special Features/Product Advantages
- Maximum efficiency thanks to ECM technology
- Front operation and access to terminal room, variable installation positions, display independent of position
- Simple installation due to PN 6/PN 10 combination flanges (with DN 40 to DN 65)
- Corrosion-resistant pump housing made of red brass for systems where oxygen entry is possible
- Automatic adjustment of the pump output in volume-flow-variable secondary hot water circulation systems with thermostatically controlling line shut-off valves
- Manual control mode allows optimum adaptation of the pump output to the system in constant-volume secondary hot water circulation systems
- System expansion by means of retrofittable interface modules for communication: Modbus, BACnet, LON, CAN, PLR etc.
- Remote control via infrared interface (IR stick/IR monitor)
Technical Data
- Permissible temperature range
- Potable water up to 3.57 mmol/l (20 °dH): 0 °C to +80 °C
- Heating water: -10 °C to +110 °C
- Mains connection 1~230 V, 50/60 Hz
- Protection class IPX4D
- Screwed connection or flange connection (depending on type) Rp 1 to DN 65
- Max. operating pressure, standard version: 6/10 bar (special version: 16 bar)
Equipment/Function
Operating Modes
- Manual control mode (n=constant)
- Δp-c for constant differential pressure
- Δp-v for variable differential pressure
- Δp-T for temperature-controlled differential pressure (programmable via IR-Stick, IR-Monitor, Modbus, BACnet, LON or CAN)
Manual Functions
- Operating mode setting
- Differential pressure setpoint setting
- Setting automatic setback operation
- Pump ON/OFF setting
- Speed setting (manual control mode)
Automatic Functions
- Variable power adjustment depending on the operating mode
- Automatic setback operation
- Deblocking function
- Soft start
- Full motor protection with integrated trip electronics
External Control Functions
- "Overriding Off" control input (possible with Stratos IF-Modules)
- "Overriding Min" control input (possible with Stratos IF-Modules)
- "Analogue In 0 - 10 V" control input (remote speed adjustment) (possible with Stratos IF-Modules)
- "Analogue In 0 - 10 V" control input (remote setpoint adjustment) (possible with Stratos IF-Modules)
Signal and Display Functions
- Collective fault signal (potential-free NC contact)
- Individual run signal (potential-free NO contact) (possible with Stratos IF-Modules)
- Fault signal light
- LC display for indication of pump data and fault codes
Data Exchange
- Infrared interface for wireless data exchange with IR-Stick/IR-Monitor
- Modbus RTU serial digital interface for connection to building automation BA via RS485 BUS system (possible with Stratos IF-Modules)
- BACnet serial digital interface MS/TP slave for connection to building automation BA via RS485 BUS system (possible with Stratos IF-Modules)
- CAN serial digital interface for connection to building automation BA via CAN BUS system (possible with Stratos IF-Modules)
- LON serial digital interface for connection to a LONWorks network (possible with Stratos IF-Modules)
- PLR serial digital interface for connection to BA via Wilo interface converter or company-specific coupling modules (possible with Stratos IF-Modules)
Dual Pump Management (Double Pump or 2 x Single Pump)
- Main/standby operation (automatic fault-actuated switchover/time-dependent pump cycling): various combinations with Stratos IF-Modules (accessories) possible
- Paralel operation (efficiency-optimised peak load activation and deactivation): various combinations with Stratos IF-Modules (accessories) possible
Equipment
- Wrench attachment point on pump body (for threaded pipe union pumps with P2≤100 W)
- For flange-end pumps: Flange versions
- Standard version for DN 40 to DN 65 pumps: PN 6/10 combination flange (PN 16 flange according to EN 1092-2) for PN 6 and PN 16 counter flanges,
- Special version for DN 40 to DN 65 pumps: PN 16 flange (according to EN 1092-2) for PN 16 counter flange,
- Plug-in position for optional extension with Wilo-IF-Modules
- Thermal insulation as standard
Materials
- Pump housing made of red brass (30/1-12 and 40/1-8 types, also grey cast iron)
- Impeller: Plastic
- Shaft: stainless steel
- Bearing: Carbon, synthetic resin impregnated
Scope of delivery
- Pump
- Including thermal insulation
- Including seals for threaded connection (loose)
- Including washers for flange screws (for nominal connection diameters DN 40 - DN 65)
- Including installation and operating instructions
Options
- Special versions for operating pressure PN 16
Accessories
- Screwed connection for threaded connection
- Adapter fittings
- IR-Stick
- IR-Monitor
- Stratos IF-Modules: Modbus, BACnet, CAN, PLR, LON, DP, Ext. Off, Ext. Min., SBM, Ext. Off/SBM