DL-E
Design
Electronically controlled glanded double pump in in-line design with flange connection and automatic power adjustment
Application
For pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cooling water systems
|
Type key
|
Example |
DL-E 50/170-7,5/2-R1 |
DL-E |
In-line double pump with electronic control |
50 |
Nominal diameter DN of the pipe connection |
170 |
Nominal impeller diameter |
7,5 |
Nominal motor power P2 in kW |
2 |
Number of poles |
R1 |
Version without pressure sensor |
Special Features/Product Advantages
- Motors with IE2 technology for higher efficiency fitted as standard
- Energy savings due to integrated electronic control
- Simple operation with red-button technology and display
- Various operating modes: main/standby operation and parallel operation
- Configurable signal relays for run and fault signals
- Configurable fault response tailored to HVAC applications
- Access disable on the pump
- Integrated full motor protection (PTC thermistor sensor) with trip electronics
- Functions and operation identical to Wilo-VeroTwin-DP-E
- High standard of corrosion protection thanks to cataphoretic coating
- Condensate drainage holes as standard
Technical Data
- Permissible temperature range -20 °C to +140 °C
- Mains connection
- 3~400 V ±%10 , 50 Hz
- 3~380 V - %5 + %10 , 60 Hz
- Koruma sınıfı IP 55
- Nominal diameter DN 40 to DN 200
- Max. operating pressure 16 bar
Description/Design
Single-stage, low-pressure double pump in in-line design with
- Switchover valve
- Mechanical seal
- Flange connection
- Lantern
- Coupling
- Drive with integrated electronic speed control
Materials
- Pump housing and lantern: EN-GJL-250
- Impeller:
- Standard version: EN-GJL-200
- Special version: G-CuSn 10
- Shaft: 1.4122
- Mechanical seal: AQEGG; other mechanical seals on request
Equipment/Function
Operating Modes
- Δp-c for constant differential pressure
- Δp-v for variable differential pressure
- PID control
- Manual control mode (n=constant)
MManual operation level
Manual Functions
- Differential pressure setpoint setting
- Speed setting (manual control mode)
- Operating mode setting
- Pump ON/OFF setting
- Configuration of all operating parameters
- Error acknowledgement
External Control Functions
- "Overriding Off" control input
- "External pump cycling" control input (effective only in double pump operation mode)
- Analogue input 0–10 V, 0–20 mA for manual control mode (DDC) and remote setpoint adjustment
- Analogue input 2–10 V, 4–20 mA for manual control mode (DDC) and remote setpoint adjustment
- Analogue input 0–10 V for actual value signal from pressure sensor
- Analogue input 2–10 V, 0-20 mA, 4–20 mA for actual value signal from pressure sensor
Signal and Display Functions
- Collective fault signal SSM
- Collective run signal SBM
Data Exchange
- Infrared interface for wireless data exchange with IR-Module/IR-Stick
- Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation
Safety Functions
- Full motor protection with integrated trip electronics
- Access disable
Dual Pump Management (Double Pump or 2 x Single Pump)
- Main/standby operation (automatic fault-actuated switchover)
- Pump cycling main/standby operation after 24 hours
- Parallel operation
- Parallel operation (efficiency-optimised peak-load activation and deactivation)
Scope of delivery
- Pump
- Installation and operating instructions
Options
- R1 version without differential pressure sensor
- L1 variant with red brass impeller (at additional charge)
- H1 variant with housing made of spheroidal cast iron (at additional charge)
Accessories
- Three mounting brackets with fixation material for installation on a base
- Blind flanges for double pump housing
- IR-Monitor, IR-Stick
- IF-Module PLR for connecting to PLR/interface converter
- IF-Module LON for connection to the LONWORKS network
- BACnet IF-Module
- Modbus IF-Module
- CAN IF-Module
- VR-HVAC control system
- Control system CCe-HVAC
- SC-HVAC control system
General notes - ErP (ecological design-) directive
- The benchmark for most efficient water pumps is MEI ≥ 0.70
- The efficiency of a pump with a trimmed impeller is usually lower than that of a pump with the full impeller diameter. The trimming of the impeller will adapt the pump to a fixed duty point, leading to reduced energy consumption. The minimum efficiency index (MEI) is based on the full impeller diameter.
- The operation of this water pump with variable duty points may be more efficient and economic when controlled, for example, by the use of a variable speed drive that matches the pump duty to the system.
- Information on benchmark efficiency is available at www.europump.org/efficiencycharts