IL


IL

Design

Glanded pump in in-line design with flange connection

Application

For pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cooling water systems



   
Type key  
Example IL 40/1604/2
IL In-line pump
40 Nominal diameter DN of the pipe connection
160 Nominal impeller diameter
4 Rated motor power P2 in kW
2 Number of poles

Special features/product advantages

  • High-efficiency motors as standard; from 0.75 kW nominal motor power: motors with IE2 technology
  • Reduced life cycle costs due to optimised efficiency
  • Standard condensate drainage holes in the motor housings
  • Can be used flexibly in air-conditioning and cooling systems, with application benefits due direct draining of condensate via optimised lantern design (patented)
  • High corrosion protection thanks to cataphoretic coating
  • Bidirectional mechanical seal with forced flushing
  • High worldwide availability of standard motors (according to Wilo specifications) and standard mechanical seals
  • Easy to install due to feet with threaded holes on pump housing


Technical Data

  • Permissible temperature range -20 °C to +140 °C
  • Mains connection 3~400 V, 50 Hz (others on request)
  • Protection class IP 55
  • Nominal diameter DN 32 to DN 250
  • Max. operating pressure 16 bar (25 bar on request)

Description/Design

  • Single-stage, low-pressure centrifugal pump in in-line design with
  • Mechanical seal
  • Flange connection with pressure measuring connection R 1/8
  • Lantern
  • Coupling
  • IEC standard motor
Materials

  • Pump housing and lantern: Standard: EN-GJL-250; optionally spheroidal cast iron EN-GJS-400-18-LT
  • Impeller: Standard: EN-GJL-200; Special version: Red brass G-CuSn 10
  • Shaft: 1.4122
  • Mechanical seal: AQEGG; other mechanical seals on request

Scope of delivery

  • Pump
  • Installation and operating instructions

Options

  • L1 variant with red brass impeller (at additional charge)
  • H1 variant with housing made of spheroidal cast iron (at additional charge)
  • P4 variant for maximum operating pressure of 25 bar (see Wilo price list)
  • Motors with efficiency class IE3, other voltages and frequencies, as well as ATEX approval on request

Accessories

  • Mounting brackets for installation on a base
  • PTC thermistor sensor, PTC resistor tripping relay
  • Special motors
  • Special mechanical seals
  • Control systems CC-HVAC, VR-HVAC and switchgear

General notes - ErP (ecological design-) directive

  • The benchmark for most efficient water pumps is MEI ≥ 0.70
  • The efficiency of a pump with a trimmed impeller is usually lower than that of a pump with the full impeller diameter. The trimming of the impeller will adapt the pump to a fixed duty point, leading to reduced energy consumption. The minimum efficiency index (MEI) is based on the full impeller diameter.
  • The operation of this water pump with variable duty points may be more efficient and economic when controlled, for example, by the use of a variable speed drive that matches the pump duty to the system.
  • Information on benchmark efficiency is available at www.europump.org/efficiencycharts