IL
Design
Glanded pump in in-line design with flange connection
Application
For pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cooling water systems
|
|
Type key |
|
Example |
IL 40/1604/2 |
IL |
In-line pump |
40 |
Nominal diameter DN of the pipe connection |
160 |
Nominal impeller diameter |
4 |
Rated motor power P2 in kW |
2 |
Number of poles |
Special features/product advantages
-
High-efficiency motors as standard; from 0.75 kW nominal motor power: motors with IE2 technology
-
Reduced life cycle costs due to optimised efficiency
-
Standard condensate drainage holes in the motor housings
-
Can be used flexibly in air-conditioning and cooling systems, with application benefits due direct draining of condensate via optimised lantern design (patented)
-
High corrosion protection thanks to cataphoretic coating
-
Bidirectional mechanical seal with forced flushing
-
High worldwide availability of standard motors (according to Wilo specifications) and standard mechanical seals
-
Easy to install due to feet with threaded holes on pump housing
Technical Data
-
Permissible temperature range -20 °C to +140 °C
-
Mains connection 3~400 V, 50 Hz (others on request)
-
Protection class IP 55
-
Nominal diameter DN 32 to DN 250
-
Max. operating pressure 16 bar (25 bar on request)
Description/Design
-
Single-stage, low-pressure centrifugal pump in in-line design with
-
Mechanical seal
-
Flange connection with pressure measuring connection R 1/8
-
Lantern
-
Coupling
-
IEC standard motor
Materials
-
Pump housing and lantern: Standard: EN-GJL-250; optionally spheroidal cast iron EN-GJS-400-18-LT
-
Impeller: Standard: EN-GJL-200; Special version: Red brass G-CuSn 10
-
Shaft: 1.4122
-
Mechanical seal: AQEGG; other mechanical seals on request
Scope of delivery
-
Pump
-
Installation and operating instructions
Options
-
L1 variant with red brass impeller (at additional charge)
-
H1 variant with housing made of spheroidal cast iron (at additional charge)
- P4 variant for maximum operating pressure of 25 bar (see Wilo price list)
- Motors with efficiency class IE3, other voltages and frequencies, as well as ATEX approval on request
Accessories
-
Mounting brackets for installation on a base
-
PTC thermistor sensor, PTC resistor tripping relay
- Special motors
- Special mechanical seals
- Control systems CC-HVAC, VR-HVAC and switchgear
General notes - ErP (ecological design-) directive
-
The benchmark for most efficient water pumps is MEI ≥ 0.70
-
The efficiency of a pump with a trimmed impeller is usually lower than that of a pump with the full impeller diameter. The trimming of the impeller will adapt the pump to a fixed duty point, leading to reduced energy consumption. The minimum efficiency index (MEI) is based on the full impeller diameter.
- The operation of this water pump with variable duty points may be more efficient and economic when controlled, for example, by the use of a variable speed drive that matches the pump duty to the system.
- Information on benchmark efficiency is available at www.europump.org/efficiencycharts